Manual motor starter - Motor protection and control - ABB Group
ABB’s Push-In Spring terminals offer unique, reliable, fast and easy connections which eliminate routine re-tightening; Main features. Handle for switching ON/OFF manually/ short-circuit current and overload protection; Adjustable current setting ranges; Large markings on setting scale for precise current setting; Disconnection function
The ABB manual motor protector (MMP) is a device that replaces the magnetic contactor and overload relay in a motor controller. The MMP uses an adjustable bimetallic for overload protection. The bimetallic has four heaters, one in each phase for quick acting overload protection and one for ambient compensation which negates the effects of
A manual motor protector is a simple, compact and economical alternative to conventional magnetic motor controllers for local control of a single motor. Upstream short-circuit and overcurrent protection in the form of either fuses or a circuit breaker is still required.
MS116-0.16 | ABB - ABB Group
The MS116-0.16 manual motor starter (also known as motor protection circuit breaker or manual motor protector) is a compact 45 mm width device with a rated operational current of Ie = 0.16 A. This device is used to manually switch on and off motors and to protect them reliably and without the need for a fuse from short-circuits, overload and ...
Detailed information for: MMP C275/3+1T - ABB Group
MMP C275/3+1T General Information. Extended Product Type: MMP C275/3+1T; Product ID: 7TCA085460R0248; EAN: 5414363167174; Catalog Description: MMP C275/3+1T Surge Protective Device; Long Description: MMP C275/3+1T 2 MODE PLUGGABLE TYPE 2 275V POWER SPD FOR 3 PHASE TT SUPPLIES, 40kA 8/20
Mechanical specification MMP 2C150/2 MMP 2C150/2/TT MMP 2C150/1+1T Temperature range -40 to +80 °C Connection type for power (upper terminals) 6 mm2 solid conductor, 4 mm2 stranded conductor - maximum torque 2 Nm for power (lower terminals) 35 mm2 solid conductor, 25 mm2 stranded conductor - maximum torque 3 Nm
The MMP surge protectors should be fully disconnected from the mains supply before insulation tests (flash tests) are performed on the electrical installation. The MMP will treat the insulation test as a transient overvoltage and control the voltage to a low level, thereby defeating the object of the test. With Furse MMPs it is only necessary
ABB Library - MMP 2C series
ABB Library is a web tool for searching for documents related to ABB products and services.
- [PDF]
Protectors - ABB
motor protector (MMP) result in a simple, compact and economical alternative to conventional magnetic motor controllers for manual operation of a single motor. Upstream short circuit and overcurrent protection in the form of fuses or a circuit breaker is required but the MMP can replace the overload relay,
Mechanical specification MMP 2B150A/2 MMP 2B150A/2/TT MMP 2B150A/1+1T Temperature range -40 to +80 °C Connection type for power 35 mm2 solid conductor, 25 mm2 stranded conductor - maximum torque 4.5 Nm for signal (remote contact) 1.5 mm2 conductor (/S option) - maximum torque 0.25 Nm Mounting Indoor, 35 mm top hat DIN rail Degree of protection ...
- 某些结果已被删除